sched: Separate out build of NUMA sched domain from __build_sched_domains
[linux-2.6/linux-acpi-2.6/ibm-acpi-2.6.git] / Documentation / thermal / sysfs-api.txt
blob70d68ce8640a0f1490f3e126f6526ab58a62a581
1 Generic Thermal Sysfs driver How To
2 =========================
4 Written by Sujith Thomas <sujith.thomas@intel.com>, Zhang Rui <rui.zhang@intel.com>
6 Updated: 2 January 2008
8 Copyright (c)  2008 Intel Corporation
11 0. Introduction
13 The generic thermal sysfs provides a set of interfaces for thermal zone devices (sensors)
14 and thermal cooling devices (fan, processor...) to register with the thermal management
15 solution and to be a part of it.
17 This how-to focuses on enabling new thermal zone and cooling devices to participate
18 in thermal management.
19 This solution is platform independent and any type of thermal zone devices and
20 cooling devices should be able to make use of the infrastructure.
22 The main task of the thermal sysfs driver is to expose thermal zone attributes as well
23 as cooling device attributes to the user space.
24 An intelligent thermal management application can make decisions based on inputs
25 from thermal zone attributes (the current temperature and trip point temperature)
26 and throttle appropriate devices.
28 [0-*]   denotes any positive number starting from 0
29 [1-*]   denotes any positive number starting from 1
31 1. thermal sysfs driver interface functions
33 1.1 thermal zone device interface
34 1.1.1 struct thermal_zone_device *thermal_zone_device_register(char *name, int trips,
35                                 void *devdata, struct thermal_zone_device_ops *ops)
37         This interface function adds a new thermal zone device (sensor) to
38         /sys/class/thermal folder as thermal_zone[0-*].
39         It tries to bind all the thermal cooling devices registered at the same time.
41         name: the thermal zone name.
42         trips: the total number of trip points this thermal zone supports.
43         devdata: device private data
44         ops: thermal zone device call-backs.
45                 .bind: bind the thermal zone device with a thermal cooling device.
46                 .unbind: unbind the thermal zone device with a thermal cooling device.
47                 .get_temp: get the current temperature of the thermal zone.
48                 .get_mode: get the current mode (user/kernel) of the thermal zone.
49                            "kernel" means thermal management is done in kernel.
50                            "user" will prevent kernel thermal driver actions upon trip points
51                            so that user applications can take charge of thermal management.
52                 .set_mode: set the mode (user/kernel) of the thermal zone.
53                 .get_trip_type: get the type of certain trip point.
54                 .get_trip_temp: get the temperature above which the certain trip point
55                                 will be fired.
57 1.1.2 void thermal_zone_device_unregister(struct thermal_zone_device *tz)
59         This interface function removes the thermal zone device.
60         It deletes the corresponding entry form /sys/class/thermal folder and unbind all
61         the thermal cooling devices it uses.
63 1.2 thermal cooling device interface
64 1.2.1 struct thermal_cooling_device *thermal_cooling_device_register(char *name,
65                                         void *devdata, struct thermal_cooling_device_ops *)
67         This interface function adds a new thermal cooling device (fan/processor/...) to
68         /sys/class/thermal/ folder as cooling_device[0-*].
69         It tries to bind itself to all the thermal zone devices register at the same time.
70         name: the cooling device name.
71         devdata: device private data.
72         ops: thermal cooling devices call-backs.
73                 .get_max_state: get the Maximum throttle state of the cooling device.
74                 .get_cur_state: get the Current throttle state of the cooling device.
75                 .set_cur_state: set the Current throttle state of the cooling device.
77 1.2.2 void thermal_cooling_device_unregister(struct thermal_cooling_device *cdev)
79         This interface function remove the thermal cooling device.
80         It deletes the corresponding entry form /sys/class/thermal folder and unbind
81         itself from all the thermal zone devices using it.
83 1.3 interface for binding a thermal zone device with a thermal cooling device
84 1.3.1 int thermal_zone_bind_cooling_device(struct thermal_zone_device *tz,
85                         int trip, struct thermal_cooling_device *cdev);
87         This interface function bind a thermal cooling device to the certain trip point
88         of a thermal zone device.
89         This function is usually called in the thermal zone device .bind callback.
90         tz: the thermal zone device
91         cdev: thermal cooling device
92         trip: indicates which trip point the cooling devices is associated with
93                  in this thermal zone.
95 1.3.2 int thermal_zone_unbind_cooling_device(struct thermal_zone_device *tz,
96                                 int trip, struct thermal_cooling_device *cdev);
98         This interface function unbind a thermal cooling device from the certain trip point
99         of a thermal zone device.
100         This function is usually called in the thermal zone device .unbind callback.
101         tz: the thermal zone device
102         cdev: thermal cooling device
103         trip: indicates which trip point the cooling devices is associated with
104                 in this thermal zone.
106 2. sysfs attributes structure
108 RO      read only value
109 RW      read/write value
111 Thermal sysfs attributes will be represented under /sys/class/thermal.
112 Hwmon sysfs I/F extension is also available under /sys/class/hwmon
113 if hwmon is compiled in or built as a module.
115 Thermal zone device sys I/F, created once it's registered:
116 /sys/class/thermal/thermal_zone[0-*]:
117         |-----type:                     Type of the thermal zone
118         |-----temp:                     Current temperature
119         |-----mode:                     Working mode of the thermal zone
120         |-----trip_point_[0-*]_temp:    Trip point temperature
121         |-----trip_point_[0-*]_type:    Trip point type
123 Thermal cooling device sys I/F, created once it's registered:
124 /sys/class/thermal/cooling_device[0-*]:
125         |-----type :                    Type of the cooling device(processor/fan/...)
126         |-----max_state:                Maximum cooling state of the cooling device
127         |-----cur_state:                Current cooling state of the cooling device
130 These two dynamic attributes are created/removed in pairs.
131 They represent the relationship between a thermal zone and its associated cooling device.
132 They are created/removed for each
133 thermal_zone_bind_cooling_device/thermal_zone_unbind_cooling_device successful execution.
135 /sys/class/thermal/thermal_zone[0-*]
136         |-----cdev[0-*]:                The [0-*]th cooling device in the current thermal zone
137         |-----cdev[0-*]_trip_point:     Trip point that cdev[0-*] is associated with
139 Besides the thermal zone device sysfs I/F and cooling device sysfs I/F,
140 the generic thermal driver also creates a hwmon sysfs I/F for each _type_ of
141 thermal zone device. E.g. the generic thermal driver registers one hwmon class device
142 and build the associated hwmon sysfs I/F for all the registered ACPI thermal zones.
143 /sys/class/hwmon/hwmon[0-*]:
144         |-----name:                     The type of the thermal zone devices.
145         |-----temp[1-*]_input:          The current temperature of thermal zone [1-*].
146         |-----temp[1-*]_critical:       The critical trip point of thermal zone [1-*].
147 Please read Documentation/hwmon/sysfs-interface for additional information.
149 ***************************
150 * Thermal zone attributes *
151 ***************************
153 type                            Strings which represent the thermal zone type.
154                                 This is given by thermal zone driver as part of registration.
155                                 Eg: "acpitz" indicates it's an ACPI thermal device.
156                                 In order to keep it consistent with hwmon sys attribute,
157                                 this should be a short, lowercase string,
158                                 not containing spaces nor dashes.
159                                 RO
160                                 Required
162 temp                            Current temperature as reported by thermal zone (sensor)
163                                 Unit: millidegree Celsius
164                                 RO
165                                 Required
167 mode                            One of the predefined values in [kernel, user]
168                                 This file gives information about the algorithm
169                                 that is currently managing the thermal zone.
170                                 It can be either default kernel based algorithm
171                                 or user space application.
172                                 RW
173                                 Optional
174                                 kernel  = Thermal management in kernel thermal zone driver.
175                                 user    = Preventing kernel thermal zone driver actions upon
176                                           trip points so that user application can take full
177                                           charge of the thermal management.
179 trip_point_[0-*]_temp           The temperature above which trip point will be fired
180                                 Unit: millidegree Celsius
181                                 RO
182                                 Optional
184 trip_point_[0-*]_type           Strings which indicate the type of the trip point
185                                 E.g. it can be one of critical, hot, passive,
186                                     active[0-*] for ACPI thermal zone.
187                                 RO
188                                 Optional
190 cdev[0-*]                       Sysfs link to the thermal cooling device node where the sys I/F
191                                 for cooling device throttling control represents.
192                                 RO
193                                 Optional
195 cdev[0-*]_trip_point            The trip point with which cdev[0-*] is associated in this thermal zone
196                                 -1 means the cooling device is not associated with any trip point.
197                                 RO
198                                 Optional
200 ******************************
201 * Cooling device  attributes *
202 ******************************
204 type                            String which represents the type of device
205                                 eg: For generic ACPI: this should be "Fan",
206                                 "Processor" or "LCD"
207                                 eg. For memory controller device on intel_menlow platform:
208                                 this should be "Memory controller"
209                                 RO
210                                 Required
212 max_state                       The maximum permissible cooling state of this cooling device.
213                                 RO
214                                 Required
216 cur_state                       The current cooling state of this cooling device.
217                                 the value can any integer numbers between 0 and max_state,
218                                 cur_state == 0 means no cooling
219                                 cur_state == max_state means the maximum cooling.
220                                 RW
221                                 Required
223 3. A simple implementation
225 ACPI thermal zone may support multiple trip points like critical/hot/passive/active.
226 If an ACPI thermal zone supports critical, passive, active[0] and active[1] at the same time,
227 it may register itself as a thermal_zone_device (thermal_zone1) with 4 trip points in all.
228 It has one processor and one fan, which are both registered as thermal_cooling_device.
229 If the processor is listed in _PSL method, and the fan is listed in _AL0 method,
230 the sys I/F structure will be built like this:
232 /sys/class/thermal:
234 |thermal_zone1:
235         |-----type:                     acpitz
236         |-----temp:                     37000
237         |-----mode:                     kernel
238         |-----trip_point_0_temp:        100000
239         |-----trip_point_0_type:        critical
240         |-----trip_point_1_temp:        80000
241         |-----trip_point_1_type:        passive
242         |-----trip_point_2_temp:        70000
243         |-----trip_point_2_type:        active0
244         |-----trip_point_3_temp:        60000
245         |-----trip_point_3_type:        active1
246         |-----cdev0:                    --->/sys/class/thermal/cooling_device0
247         |-----cdev0_trip_point:         1       /* cdev0 can be used for passive */
248         |-----cdev1:                    --->/sys/class/thermal/cooling_device3
249         |-----cdev1_trip_point:         2       /* cdev1 can be used for active[0]*/
251 |cooling_device0:
252         |-----type:                     Processor
253         |-----max_state:                8
254         |-----cur_state:                0
256 |cooling_device3:
257         |-----type:                     Fan
258         |-----max_state:                2
259         |-----cur_state:                0
261 /sys/class/hwmon:
263 |hwmon0:
264         |-----name:                     acpitz
265         |-----temp1_input:              37000
266         |-----temp1_crit:               100000