1 title: Rittal CMC-III LCP: Air Out Temperature
2 agents: snmp
3 catalog: hw/environment/rittal
4 license: GPL
5 distribution: check_mk
6 description:
7  Note: This check is obsolete, the individual temperatures (top, middle, bottom) are
8    also available through the cmciii.temp_in_out check.
9  This check monitors the temperature of the outflowing air of
10  Rittal CMC-III LCP devices. Temperatures at top, middle and bottom
11  of the device are captured, as well as the average value given
12  by the device.
13  No limits are set in the check, since limits are configured in the
14  Rittal device itself. The state given by the Rittal device is
15  taken as the state of the check as follows:
16  If the Rittal device returns {OK}, the check is {OK}. Otherwise
17  the check is {CRIT}.
18  Furthermore, the lower and upper warning and critical limits configured
19  in the device are extracted and used as limits for the
20  average temperature read from the device.
22 item:
23  None
25 inventory:
26  None