Refactoring: Changed all check parameters starting with an 'o' to the new rulespec...
[check_mk.git] / checks / liebert_cooling
blobd3d9d13622b52c52f7674f2eb2c83e3c3f133a17
1 #!/usr/bin/python
2 # -*- encoding: utf-8; py-indent-offset: 4 -*-
3 # +------------------------------------------------------------------+
4 # | ____ _ _ __ __ _ __ |
5 # | / ___| |__ ___ ___| | __ | \/ | |/ / |
6 # | | | | '_ \ / _ \/ __| |/ / | |\/| | ' / |
7 # | | |___| | | | __/ (__| < | | | | . \ |
8 # | \____|_| |_|\___|\___|_|\_\___|_| |_|_|\_\ |
9 # | |
10 # | Copyright Mathias Kettner 2017 mk@mathias-kettner.de |
11 # +------------------------------------------------------------------+
13 # This file is part of Check_MK.
14 # The official homepage is at http://mathias-kettner.de/check_mk.
16 # check_mk is free software; you can redistribute it and/or modify it
17 # under the terms of the GNU General Public License as published by
18 # the Free Software Foundation in version 2. check_mk is distributed
19 # in the hope that it will be useful, but WITHOUT ANY WARRANTY; with-
20 # out even the implied warranty of MERCHANTABILITY or FITNESS FOR A
21 # PARTICULAR PURPOSE. See the GNU General Public License for more de-
22 # tails. You should have received a copy of the GNU General Public
23 # License along with GNU Make; see the file COPYING. If not, write
24 # to the Free Software Foundation, Inc., 51 Franklin St, Fifth Floor,
25 # Boston, MA 02110-1301 USA.
27 # example output
28 # .1.3.6.1.4.1.476.1.42.3.9.20.1.10.1.2.1.5078 Cooling Capacity (Primary)
29 # .1.3.6.1.4.1.476.1.42.3.9.20.1.20.1.2.1.5078 0
30 # .1.3.6.1.4.1.476.1.42.3.9.20.1.30.1.2.1.5078 %
32 factory_settings['liebert_cooling_default_levels'] = {
33 'levels': (80, 90),
37 def inventory_liebert_cooling(parsed):
38 for key, values in parsed.iteritems():
39 if not "Unavailable" in values[0]:
40 yield (key, {})
43 def check_liebert_cooling(item, params, parsed):
44 for values in parsed.itervalues():
45 if not "Unavailable" in values[0]:
46 value = float(values[0])
47 unit = values[1]
48 warn, crit = params['levels']
49 yield 0, "%s%s" % (value, unit), [('filehandler_perc', value, warn, crit)]
51 state = levels_liebert(value, warn, crit, 'higher')
52 if state > 0:
53 yield state, "(warn/crit below %s%s/%s%s)" % (warn, unit, crit, unit)
56 check_info['liebert_cooling'] = {
57 'parse_function': parse_liebert,
58 'inventory_function': inventory_liebert_cooling,
59 'check_function': check_liebert_cooling,
60 'service_description': '%s',
61 'snmp_info': (
62 '.1.3.6.1.4.1.476.1.42.3.9.20.1',
64 '10.1.2.1.5078', #LIEBERT-GP-FLExible-MIB: lgpFlexibleEntryDataLabel
65 '20.1.2.1.5078', #LIEBERT-GP-FLExible-MIB: lgpFlexibleEntryValue
66 '30.1.2.1.5078', #LIEBERT-GP-FLExible-MIB: lgpFlexibleEntryUnitsOfMeasure
67 ]),
68 'snmp_scan_function': scan_liebert,
69 'includes': ['liebert.include'],
70 'has_perfdata': True,
71 'default_levels_variable': 'liebert_cooling_default_levels',