Refactoring: Changed all check parameters starting with an 'o' to the new rulespec...
[check_mk.git] / checks / ups_socomec_out_source
blob6891628a9732d3d93696d9552f2b320a2d16db9c
1 #!/usr/bin/python
2 # -*- encoding: utf-8; py-indent-offset: 4 -*-
3 # +------------------------------------------------------------------+
4 # | ____ _ _ __ __ _ __ |
5 # | / ___| |__ ___ ___| | __ | \/ | |/ / |
6 # | | | | '_ \ / _ \/ __| |/ / | |\/| | ' / |
7 # | | |___| | | | __/ (__| < | | | | . \ |
8 # | \____|_| |_|\___|\___|_|\_\___|_| |_|_|\_\ |
9 # | |
10 # | Copyright Mathias Kettner 2014 mk@mathias-kettner.de |
11 # +------------------------------------------------------------------+
13 # This file is part of Check_MK.
14 # The official homepage is at http://mathias-kettner.de/check_mk.
16 # check_mk is free software; you can redistribute it and/or modify it
17 # under the terms of the GNU General Public License as published by
18 # the Free Software Foundation in version 2. check_mk is distributed
19 # in the hope that it will be useful, but WITHOUT ANY WARRANTY; with-
20 # out even the implied warranty of MERCHANTABILITY or FITNESS FOR A
21 # PARTICULAR PURPOSE. See the GNU General Public License for more de-
22 # tails. You should have received a copy of the GNU General Public
23 # License along with GNU Make; see the file COPYING. If not, write
24 # to the Free Software Foundation, Inc., 51 Franklin St, Fifth Floor,
25 # Boston, MA 02110-1301 USA.
28 def inventory_ups_socomec_out_source(info):
29 if info:
30 return [(None, None)]
33 def check_ups_socomec_out_source(_no_item, _no_params, info):
35 # This is from the old (v5.01) MIB and is incompatible with the new one below
36 # ups_socomec_source_states = {
37 # 1: (3, "Other"),
38 # 2: (2, "Offline"),
39 # 3: (0, "Normal"),
40 # 4: (1, "Internal Maintenance Bypass"),
41 # 5: (2, "On battery"),
42 # 6: (0, "Booster"),
43 # 7: (0, "Reducer"),
44 # 8: (0, "Standby"),
45 # 9: (0, "Eco mode"),
46 # }
48 # This is from the new (v6) MIB
49 ups_socomec_source_states = {
50 1: (3, "Unknown"),
51 2: (2, "On inverter"),
52 3: (0, "On mains"),
53 4: (0, "Eco mode"),
54 5: (1, "On bypass"),
55 6: (0, "Standby"),
56 7: (1, "On maintenance bypass"),
57 8: (2, "UPS off"),
58 9: (0, "Normal mode"),
61 return ups_socomec_source_states[int(info[0][0])]
64 check_info['ups_socomec_out_source'] = {
65 "inventory_function": inventory_ups_socomec_out_source,
66 "check_function": check_ups_socomec_out_source,
67 "service_description": "Output Source",
68 "snmp_info": (".1.3.6.1.4.1.4555.1.1.1.1.4", ["1"]),
69 "snmp_scan_function": lambda oid: oid(".1.3.6.1.2.1.1.2.0") == ".1.3.6.1.4.1.4555.1.1.1",